GCK Draw-Out Low Voltage Switchgear Electrical Cabinet

Short Description:

GCK draw-out low voltage switchgear electrical cabinet is composed of power distribution center (PC) cabinet and motor control center (MCC). It is suitable for power users such as power plants, substations, industrial and mining enterprises as ac 50Hz, the maximum working voltage to 660V, the maximum working current to 3150A in the distribution system. As power distribution, motor control and lighting and other power distribution equipment conversion and distribution control.


Product Detail

Product Tags

Main features

1. GCK1 and GCJ1 are assembled composite structures and the basic skeleton is assembled by special profiles.
2. The cabinet frame. part size and opening size change according to the basic modulus E=25mm.
3. In MCC scheme, he cabinet is diveded into five areas, horizontal bus area, vertical bus area, function unit area, cable room and neutral grounding bus area, the districts are isolated from each other to ensure the normal operation of line and effectively prevent the fault from expanding.
4. Because all the structures of the frame are fastened and connected by screws, the welding deformation and stress are avoided and the accuracy is improved.
5. Parts have strong universality, good applicability and high standardization.
6. The extraction and insertion of functional unit are lever operation and the operation with rolling bearings is light and reliable .

Use environmental conditions

1. Ambient air temperature: -5~+40 and the average temperature should not exceed +35 in 24h.
2. Install and use indoors. Altitude above sea level for operation site should not exceed 2000M.
3. Relative humidity should not exceed 50% at max temperature +40. Higher relative humidity is allowed at lower temperature. Ex. 90% at +20. But in view of the temperature change, it is possible that moderate dews will produce casually.
4. Installation gradient not exceed 5.
5. Install in the places without fierce vibration and shock and the sites insufficient to erode the electrical components.
6. Any specific requirement, consult with manufactory.

Main technical parameters

Protection level IP40 . IP30
Rated working voltage Ac .380v
Frequency 50Hz
Rated insulation voltage 660V
Working conditions
Environment Indoor
Altitude ≤2000m
Ambient temperature -5℃ – +40℃
The min temperature under store and transportation <30℃
Relative humidity ≤90%
Capacity of control motor (KW) 0.4 – 155

Rated current

(A)

Horizontal bus bar 1600.  2000. 3150
Vertical bus bar 630. 800
Contact connector of main circuit 200 . 400
Feeding circuit 1600
Max current  PC cabinet 630
Power receiving circuit MCC cabinet 1000.1600.2000.2500.3150
Rated short time withstand current KA
Virtual value 50. 80
Peak value 105.176
Line frequency withstand voltage V/1min 2500

Internal structure

product-description1