Drawable Low Voltage Switchgear Electrical Cabinet
Environment condition
1. Ambient air temperature: -5℃~+40℃ and the average temperature should not exceed +35 in 24h.
2. Install and use indoors. Altitude above sea level for operation site should not exceed 2000M.
3. Relative humidity should not exceed 50% at max temperature +40. Higher relative humidity is allowed at lower temperature. Ex. 90% at +20. But in view of the temperature change, it is possible that moderate dews will produce casually.
4. Installation gradient not exceed.
5. Install in the places without fierce vibration and shock and the sites insufficient to erode the electrical components.
6. Any specific requirement, consult with manufactory.
Technical parameters
Rated working voltage(v) | Rated insulation voltage(V) | Rated working current(A) | Rated short time withstand current effective value/Peak | Protection grade | ||
Horizontal bus bar | Vertical bus bar | Horizontal bus bar | Vertical bus bar | Dimension H x W x D | ||
380 660 | 660 1000 | 630-5000 | 800-2000 | 50-100/105-250 | 60/130-150 | 2200×600(800.1000) x800(1000) |