YB6-11/15/33/0.4KV 50-2000KVA American Prefabricated Outdoor Transformer Box Substation
Model description
Product rated parameters
Rated voltage |
10KV/0.4KV |
Rated voltage of HV |
10kV |
Max. voltage of HV |
12KV |
Rated voltage of LV |
0.4KV |
Rated frequency |
50Hz |
Thermal stability capacity of HV breaker |
20KA/2S |
Rated short circuit breaking capacity of LV main circuit switch |
35KA |
Rated shot circuit breaking capacity of LV distribution circuit switch |
35KA |
Transferred current of HV load switch |
>1500A |
Noise level |
<50dB |
Enclosure protection grade |
Not less than IP3X |
Insulation level
Rated voltage (KV) |
Transformer |
Switch to earth and inter phase |
Switch isolating inter fracture |
0.4 |
Power frequency withstand voltage (KV) |
35 |
42 |
48 |
-2.5 |
Peak impulse withstand value (KV) |
75 |
75 |
85 |
-2.5 |
Features
1. Compact structure with small volume, the volume is 1/3-1/5 of European style substation in same capacity. It reduces the floor space efficiently.
2. Whole sealing and full insulated structure ,no need insulation distance. This can protect personal safety.
3. High voltage wiring can use both in looped network and terminal with high reliability and flexibility.
4. The transformer is with excellent performance, low loss, low Noise, low temperature rise, high overload capacity, strong impact resistant ability and high anti-short circuit capacity.
5. Cable head with two type: 200A elbow connector and 600A “T” type fixed cable connector. Both can equip with all insulated Zn O lightning conductor. 200A elbow connector can use with load plug and with the function of insulation switch.
Transformer parameters
Load switch of parameter
Environmental conditions
-Ambient temperature: MAX.+40 ℃, MINI. -30℃
-Altitude: ≤1000m
-Wind speed: About 34m/s (≤700Pa)
-Humidity: Average daily relative humidity ≤95%; Average monthly relative humidity ≤90%
-Shockproof: Level acceleration: 0.4m/s2, Vertical acceleration ≤0.15m/s2
-Gradient of installation position: ≤3°
-Installing environment: Ambient has not been obviously polluted by corrosive or fammable gas, and there is no strong feeling of shock.